Lining Systems for Potable Water
Carbozinc 8703
Tank Ratings
|
System # |
1 |
NSF 600 |
Y |
UL Tank Size |
20,000 gallons |
UL # of Coats |
1 |
UL Max DFT |
2 mils |
UL Cure Time |
2 weeks |
UL Thinner |
20% max of either Thinner 33 or 21 |
Pipe, Valves, and Fittings
|
System # |
1 |
NSF 600 |
Y |
UL Pipe Size |
118 inches |
UL Valve Size |
Not rated |
UL # of Coats |
1 |
UL Max DFT |
2 mils |
UL Cure Time |
2 weeks |
UL Thinner |
20% max of either Thinner 33 or 21 |
Carboguard 635 VOC
Tank Ratings
|
System # |
1 |
NSF 600 |
Y |
UL Tank Size |
40,000 gallons |
UL # of Coats |
1 to 2 |
UL Max DFT |
16 mils |
UL Cure Time |
7 days |
UL Thinner |
10% max of Thinner #76 |
Pipe, Valves, and Fittings
|
System # |
1 |
NSF 600 |
Y |
UL Pipe Size |
Not rated |
UL Valve Size |
4" |
UL # of Coats |
1 to 2 |
UL Max DFT |
16 mils |
UL Cure Time |
7 days |
UL Thinner |
10% max of Thinner #76 |
Carboguard 691
Tank Ratings
|
System # |
1 |
NSF 600 |
Y |
UL Tank Size |
30,000 gallons |
UL # of Coats |
1 to 2 |
UL Max DFT |
20 mils (1 coat); 30 mils (2 coats) |
UL Cure Time |
7 days |
UL Thinner |
12.5% max of Thinner #2 |
Pipe, Valves, and Fittings
|
System # |
1 |
NSF 600 |
N |
UL Pipe Size |
Not rated |
UL Valve Size |
4" |
UL # of Coats |
1 to 2 |
UL Max DFT |
20 mils (1 coat); 30 mils (2 coats) |
UL Cure Time |
7 days |
UL Thinner |
12.5% max of Thinner #2 |
Carboguard 891 VOC
Tank Ratings
|
System # |
2 |
NSF 600 |
Y |
UL Tank Size |
70,000 gallons |
UL # of Coats |
2 to 3 |
UL Max DFT |
20 mils |
UL Cure Time |
7 days |
UL Thinner |
Max 13 oz per gallon of Thinner 2 or 225 E |
Pipe, Valves, and Fittings
|
System # |
2 |
NSF 600 |
Y |
UL Pipe Size |
Not rated |
UL Valve Size |
Not rated |
UL # of Coats |
2 to 3 |
UL Max DFT |
20 mils |
UL Cure Time |
7 days |
UL Thinner |
Max of 13 oz per gallon of Thinner #2 or 225 E |
Hydroplate 1080
Tank Ratings
|
System # |
1 |
NSF 600 |
Y |
UL Tank Size |
30,000 gallons |
UL # of Coats |
1 to 2 |
UL Max DFT |
20 mils (1 coat); 30 mils (2 coats) |
UL Cure Time |
7 days |
UL Thinner |
12.5% max of Thinner 2 |
Pipe, Valves, and Fittings
|
System # |
1 |
NSF 600 |
Y |
UL Pipe Size |
Not rated |
UL Valve Size |
4 inches |
UL # of Coats |
1 to 2 |
UL Max DFT |
20 mils (1 coat); 30 mils (2 coats) |
UL Cure Time |
7 days |
UL Thinner |
12.5% max of Thinner 2 |
Hydroplate 1086
Tank Ratings
|
System # |
1 |
NSF 600 |
Y |
UL Tank Size |
50 gallons |
UL # of Coats |
2 to 3 |
UL Max DFT |
20 mils |
UL Cure Time |
14 days |
UL Thinner |
10% max of Thinner 225E |
Pipe, Valves, and Fittings
|
System # |
1 |
NSF 600 |
Y |
UL Pipe Size |
15 inches |
UL Valve Size |
1.5 inches |
UL # of Coats |
2 to 3 |
UL Max DFT |
20 mils |
UL Cure Time |
14 days |
UL Thinner |
10% max of Thinner 225E |
Hydroplate 1100
Tank Ratings
|
System # |
1 |
NSF 600 |
Y |
UL Tank Size |
500 gallons |
UL # of Coats |
1 to 2 |
UL Max DFT |
50 mils |
UL Cure Time |
4 days |
UL Thinner |
N/A |
Pipe, Valves, and Fittings
|
System # |
1 |
NSF 600 |
Y |
UL Pipe Size |
12 inches |
UL Valve Size |
4 inches |
UL # of Coats |
1 to 2 |
UL Max DFT |
50 mils |
UL Cure Time |
4 days |
UL Thinner |
N/A |
Hydroplate 6500
Tank Ratings
|
System # |
1 |
NSF 600 |
Y |
UL Tank Size |
> 200,000 gallons |
UL # of Coats |
1 to 2 |
UL Max DFT |
125 mils |
UL Cure Time |
1 days |
UL Thinner |
N/A |
Carboguard 891 VOC (14 Day)
Tank Ratings
|
System # |
1 |
NSF 600 |
N |
UL Tank Size |
50 gallons |
UL # of Coats |
2 to 3 |
UL Max DFT |
20 mils |
UL Cure Time |
14 days |
UL Thinner |
Max 13 oz per gallon of Thinner 2 or 225 E |
Pipe, Valves, and Fittings
|
System # |
1 |
NSF 600 |
N |
UL Pipe Size |
15" |
UL Valve Size |
1.5" |
UL # of Coats |
2 to 3 |
UL Max DFT |
20 mils |
UL Cure Time |
14 days |
UL Thinner |
Max of 13 oz per gallon of Thinner #2 or 225 E |
Plasite 4110
Tank Ratings
|
System # |
1 |
NSF 600 |
Y |
NSF Tank Size |
600 gallons |
NSF # of Coats |
2-3 |
NSF Max DFT |
45 mils |
NSF Cure Time |
Recoat- 10 hours; Final Cure- 4 hours forced cure at 200 F |
NSF Thinner |
Max 20% of Plasite Thinner #20 by volume |
Pipe, Valves, and Fittings
|
System # |
1 |
NSF 600 |
N |
NSF Pipe Size |
Not Rated |
NSF Valve Size |
Not Rated |
NSF # of Coats |
N/A |
NSF Max DFT |
N/A |
NSF Cure Time |
N/A |
NSF Thinner |
N/A |
**Plasite 4110 was tested and certified by NSF's lab |
Plasite 4500
Tank Ratings
|
System # |
1 |
NSF 600 |
Y |
UL Tank Size |
5 gallons |
UL # of Coats |
1 |
UL Max DFT |
50 mils |
UL Cure Time |
3 days |
UL Thinner |
N/A |
Pipe, Valves, and Fittings
|
System # |
1 |
NSF 600 |
Y |
UL Pipe Size |
4" |
UL Valve Size |
Not rated |
UL # of Coats |
1 |
UL Max DFT |
50 mils |
UL Cure Time |
3 days |
UL Thinner |
N/A |
Plasite 4500 S
Tank Ratings
|
System # |
1 |
NSF 600 |
Y |
UL Tank Size |
1000 gallons |
UL # of Coats |
1 |
UL Max DFT |
60 mils |
UL Cure Time |
7 days |
UL Thinner |
N/A |
Pipe, Valves, and Fittings
|
System # |
1 |
NSF 600 |
Y |
UL Pipe Size |
42" |
UL Valve Size |
Not rated |
UL # of Coats |
1 |
UL Max DFT |
60 mils |
UL Cure Time |
7 days |
UL Thinner |
N/A |
Plasite 4550 HT
Tank Ratings
|
System # |
1 |
NSF 600 |
Y |
NSF Tank Size |
3,000 gallons |
NSF # of Coats |
1-2 |
NSF Max DFT |
40 mils |
NSF Cure Time |
Recoat - 4.5 hrs; Final Cure - 48 hrs at 75℉ |
NSF Thinner |
N/A |
Pipe, Valves, and Fittings
|
System # |
1 |
NSF 600 |
N |
NSF Pipe Size |
Not Rated |
NSF Valve Size |
Not Rated |
NSF # of Coats |
N/A |
NSF Max DFT |
N/A |
NSF Cure Time |
N/A |
NSF Thinner |
N/A |
Phenoline 311 Primer
Tank Ratings
|
System # |
1 |
NSF 600 |
Y |
UL Tank Size |
200 gallons |
UL # of Coats |
1 |
UL Max DFT |
3 mils |
UL Cure Time |
7 days |
UL Thinner |
Max 5% of Thinner 76 or 225 E |
Pipe, Valves, and Fittings
|
System # |
1 |
NSF 600 |
Y |
UL Pipe Size |
24" |
UL Valve Size |
Not rated |
UL # of Coats |
1 |
UL Max DFT |
3 mils |
UL Cure Time |
7 days |
UL Thinner |
Max of 5% of Thinner 76 or 225 E |
Phenoline Tank Shield
Tank Ratings
|
System # |
1 |
NSF 600 |
Y |
UL Tank Size |
500 gallons |
UL # of Coats |
1 to 2 |
UL Max DFT |
50 mils |
UL Cure Time |
4 days |
UL Thinner |
N/A |
Pipe, Valves, and Fittings
|
System # |
1 |
NSF 600 |
Y |
UL Pipe Size |
12" |
UL Valve Size |
4" |
UL # of Coats |
1 to 2 |
UL Max DFT |
50 mils |
UL Cure Time |
4 days |
UL Thinner |
N/A |
Phenoline Tank Shield FP
Tank Ratings
|
System # |
1 |
NSF 600 |
Y |
UL Tank Size |
6,000 gallons |
UL # of Coats |
1 |
UL Max DFT |
30 mils |
UL Cure Time |
4 Days |
UL Thinner |
N/A |
Pipe, Valves, and Fittings
|
System # |
1 |
NSF 600 |
N |
UL Pipe Size |
Not Rated |
UL Valve Size |
Not Rated |
UL # of Coats |
N/A |
UL Max DFT |
N/A |
UL Cure Time |
N/A |
UL Thinner |
N/A |
Reactamine 760
Tank Ratings
|
System # |
1 |
NSF 600 |
Y |
UL Tank Size |
≥ 50 gallons |
UL # of Coats |
1 to 2 |
UL Max DFT |
300 mils |
UL Cure Time |
4 hours |
UL Thinner |
N/A |
Pipe, Valves, and Fittings
|
System # |
1 |
NSF 600 |
Y |
UL Pipe Size |
14" |
UL Valve Size |
Not rated |
UL # of Coats |
1 to 2 |
UL Max DFT |
300 mils |
UL Cure Time |
4 hours |
UL Thinner |
N/A |
Reactamine 760 HB
Tank Ratings
|
System # |
1 |
NSF 600 |
Y |
UL Tank Size |
50 gallons |
UL # of Coats |
1 to 2 |
UL Max DFT |
300 mils |
UL Cure Time |
4 hours |
UL Thinner |
N/A |
Pipe, Valves, and Fittings
|
System # |
1 |
NSF 600 |
Y |
UL Pipe Size |
14" |
UL Valve Size |
Not rated |
UL # of Coats |
1 to 2 |
UL Max DFT |
300 mils |
UL Cure Time |
4 hours |
UL Thinner |
N/A |
Polyclad 767
Tank Ratings
|
System # |
1 |
NSF 600 |
Y |
UL Tank Size |
1000 gallons |
UL # of Coats |
1 |
UL Max DFT |
120 mils |
UL Cure Time |
Not Listed |
UL Thinner |
N/A |
Pipe, Valves, and Fittings
|
System # |
1 |
NSF 600 |
Y |
UL Pipe Size |
12" |
UL Valve Size |
12" |
UL # of Coats |
1 |
UL Max DFT |
120 mils |
UL Cure Time |
Not Listed |
UL Thinner |
N/A |
Polyclad 767 Slow Set
Tank Ratings
|
System # |
1 |
NSF 600 |
Y |
UL Tank Size |
1000 gallons |
UL # of Coats |
1 |
UL Max DFT |
120 mils |
UL Cure Time |
Not Listed |
UL Thinner |
N/A |
Pipe, Valves, and Fittings
|
System # |
1 |
NSF 600 |
Y |
UL Pipe Size |
12" |
UL Valve Size |
12" |
UL # of Coats |
1 |
UL Max DFT |
120 mils |
UL Cure Time |
Not Listed |
UL Thinner |
N/A |
Polyclad 767 Fast Set
Tank Ratings
|
System # |
1 |
NSF 600 |
Y |
UL Tank Size |
1000 gallons |
UL # of Coats |
1 |
UL Max DFT |
120 mils |
UL Cure Time |
Not Listed |
UL Thinner |
N/A |
Pipe, Valves, and Fittings
|
System # |
1 |
NSF 600 |
Y |
UL Pipe Size |
12" |
UL Valve Size |
12" |
UL # of Coats |
1 |
UL Max DFT |
120 mils |
UL Cure Time |
Not Listed |
UL Thinner |
N/A |
*All Systems Certified by UL to Meet the Requirements of NSF 61/NSF 600