Resources

Lining Systems for Potable Water

Carbozinc 8703

Tank Ratings
System # 1
NSF 600 Y
UL Tank Size 20,000 gallons
UL # of Coats 1
UL Max DFT 2 mils
UL Cure Time 2 weeks
UL Thinner 20% max of either Thinner 33 or 21
Pipe, Valves, and Fittings
System # 1
NSF 600 Y
UL Pipe Size 118 inches
UL Valve Size Not rated
UL # of Coats 1
UL Max DFT 2 mils
UL Cure Time 2 weeks
UL Thinner 20% max of either Thinner 33 or 21

Carboguard 635 VOC

Tank Ratings
System # 1
NSF 600 Y
UL Tank Size 40,000 gallons
UL # of Coats 1 to 2
UL Max DFT 16 mils
UL Cure Time 7 days
UL Thinner 10% max of Thinner #76
Pipe, Valves, and Fittings
System # 1
NSF 600 Y
UL Pipe Size Not rated
UL Valve Size 4"
UL # of Coats 1 to 2
UL Max DFT 16 mils
UL Cure Time 7 days
UL Thinner 10% max of Thinner #76

Carboguard 691

Tank Ratings
System # 1
NSF 600 Y
UL Tank Size 30,000 gallons
UL # of Coats 1 to 2
UL Max DFT 20 mils (1 coat); 30 mils (2 coats)
UL Cure Time 7 days
UL Thinner 12.5% max of Thinner #2
Pipe, Valves, and Fittings
System # 1
NSF 600 N
UL Pipe Size Not rated
UL Valve Size 4"
UL # of Coats 1 to 2
UL Max DFT 20 mils (1 coat); 30 mils (2 coats)
UL Cure Time 7 days
UL Thinner 12.5% max of Thinner #2

Carboguard 891 VOC

Tank Ratings
System # 2
NSF 600 Y
UL Tank Size 70,000 gallons
UL # of Coats 2 to 3
UL Max DFT 20 mils
UL Cure Time 7 days
UL Thinner Max 13 oz per gallon of Thinner 2 or 225 E
Pipe, Valves, and Fittings
System # 2
NSF 600 Y
UL Pipe Size Not rated
UL Valve Size Not rated
UL # of Coats 2 to 3
UL Max DFT 20 mils
UL Cure Time 7 days
UL Thinner Max of 13 oz per gallon of Thinner #2 or 225 E

Hydroplate 1080

Tank Ratings
System # 1
NSF 600 Y
UL Tank Size 30,000 gallons
UL # of Coats 1 to 2
UL Max DFT 20 mils (1 coat); 30 mils (2 coats)
UL Cure Time 7 days
UL Thinner 12.5% max of Thinner 2
Pipe, Valves, and Fittings
System # 1
NSF 600 Y
UL Pipe Size Not rated
UL Valve Size 4 inches
UL # of Coats 1 to 2
UL Max DFT 20 mils (1 coat); 30 mils (2 coats)
UL Cure Time 7 days
UL Thinner 12.5% max of Thinner 2

Hydroplate 1086

Tank Ratings
System # 1
NSF 600 Y
UL Tank Size 50 gallons
UL # of Coats 2 to 3
UL Max DFT 20 mils
UL Cure Time 14 days
UL Thinner 10% max of Thinner 225E
Pipe, Valves, and Fittings
System # 1
NSF 600 Y
UL Pipe Size 15 inches
UL Valve Size 1.5 inches
UL # of Coats 2 to 3
UL Max DFT 20 mils
UL Cure Time 14 days
UL Thinner 10% max of Thinner 225E

Hydroplate 1100

Tank Ratings
System # 1
NSF 600 Y
UL Tank Size 500 gallons
UL # of Coats 1 to 2
UL Max DFT 50 mils
UL Cure Time 4 days
UL Thinner N/A
Pipe, Valves, and Fittings
System # 1
NSF 600 Y
UL Pipe Size 12 inches
UL Valve Size 4 inches
UL # of Coats 1 to 2
UL Max DFT 50 mils
UL Cure Time 4 days
UL Thinner N/A

Hydroplate 6500

Tank Ratings
System # 1
NSF 600 Y
UL Tank Size > 200,000 gallons
UL # of Coats 1 to 2
UL Max DFT 125 mils
UL Cure Time 1 days
UL Thinner N/A

Carboguard 891 VOC (14 Day)

Tank Ratings
System # 1
NSF 600 N
UL Tank Size 50 gallons
UL # of Coats 2 to 3
UL Max DFT 20 mils
UL Cure Time 14 days
UL Thinner Max 13 oz per gallon of Thinner 2 or 225 E
Pipe, Valves, and Fittings
System # 1
NSF 600 N
UL Pipe Size 15"
UL Valve Size 1.5"
UL # of Coats 2 to 3
UL Max DFT 20 mils
UL Cure Time 14 days
UL Thinner Max of 13 oz per gallon of Thinner #2 or 225 E

Plasite 4110

Tank Ratings
System # 1
NSF 600 Y
NSF Tank Size 600 gallons
NSF # of Coats 2-3
NSF Max DFT 45 mils
NSF Cure Time Recoat- 10 hours; Final Cure- 4 hours forced cure at 200 F
NSF Thinner Max 20% of Plasite Thinner #20 by volume
Pipe, Valves, and Fittings
System # 1
NSF 600 N
NSF Pipe Size Not Rated
NSF Valve Size Not Rated
NSF # of Coats N/A
NSF Max DFT N/A
NSF Cure Time N/A
NSF Thinner N/A
**Plasite 4110 was tested and certified by NSF's lab

Plasite 4500

Tank Ratings
System # 1
NSF 600 Y
UL Tank Size 5 gallons
UL # of Coats 1
UL Max DFT 50 mils
UL Cure Time 3 days
UL Thinner N/A
Pipe, Valves, and Fittings
System # 1
NSF 600 Y
UL Pipe Size 4"
UL Valve Size Not rated
UL # of Coats 1
UL Max DFT 50 mils
UL Cure Time 3 days
UL Thinner N/A

Plasite 4500 S

Tank Ratings
System # 1
NSF 600 Y
UL Tank Size 1000 gallons
UL # of Coats 1
UL Max DFT 60 mils
UL Cure Time 7 days
UL Thinner N/A
Pipe, Valves, and Fittings
System # 1
NSF 600 Y
UL Pipe Size 42"
UL Valve Size Not rated
UL # of Coats 1
UL Max DFT 60 mils
UL Cure Time 7 days
UL Thinner N/A

Plasite 4550 HT

Tank Ratings
System # 1
NSF 600 Y
NSF Tank Size 3,000 gallons
NSF # of Coats 1-2
NSF Max DFT 40 mils
NSF Cure Time Recoat - 4.5 hrs; Final Cure - 48 hrs at 75℉
NSF Thinner N/A
Pipe, Valves, and Fittings
System # 1
NSF 600 N
NSF Pipe Size Not Rated
NSF Valve Size Not Rated
NSF # of Coats N/A
NSF Max DFT N/A
NSF Cure Time N/A
NSF Thinner N/A

Phenoline 311 Primer

Tank Ratings
System # 1
NSF 600 Y
UL Tank Size 200 gallons
UL # of Coats 1
UL Max DFT 3 mils
UL Cure Time 7 days
UL Thinner Max 5% of Thinner 76 or 225 E
Pipe, Valves, and Fittings
System # 1
NSF 600 Y
UL Pipe Size 24"
UL Valve Size Not rated
UL # of Coats 1
UL Max DFT 3 mils
UL Cure Time 7 days
UL Thinner Max of 5% of Thinner 76 or 225 E

Phenoline Tank Shield

Tank Ratings
System # 1
NSF 600 Y
UL Tank Size 500 gallons
UL # of Coats 1 to 2
UL Max DFT 50 mils
UL Cure Time 4 days
UL Thinner N/A
Pipe, Valves, and Fittings
System # 1
NSF 600 Y
UL Pipe Size 12"
UL Valve Size 4"
UL # of Coats 1 to 2
UL Max DFT 50 mils
UL Cure Time 4 days
UL Thinner N/A

Phenoline Tank Shield FP

Tank Ratings
System # 1
NSF 600 Y
UL Tank Size 6,000 gallons
UL # of Coats 1
UL Max DFT 30 mils
UL Cure Time 4 Days
UL Thinner N/A
Pipe, Valves, and Fittings
System # 1
NSF 600 N
UL Pipe Size Not Rated
UL Valve Size Not Rated
UL # of Coats N/A
UL Max DFT N/A
UL Cure Time N/A
UL Thinner N/A

Reactamine 760

Tank Ratings
System # 1
NSF 600 Y
UL Tank Size ≥ 50 gallons
UL # of Coats 1 to 2
UL Max DFT 300 mils
UL Cure Time 4 hours
UL Thinner N/A
Pipe, Valves, and Fittings
System # 1
NSF 600 Y
UL Pipe Size 14"
UL Valve Size Not rated
UL # of Coats 1 to 2
UL Max DFT 300 mils
UL Cure Time 4 hours
UL Thinner N/A

Reactamine 760 HB

Tank Ratings
System # 1
NSF 600 Y
UL Tank Size 50 gallons
UL # of Coats 1 to 2
UL Max DFT 300 mils
UL Cure Time 4 hours
UL Thinner N/A
Pipe, Valves, and Fittings
System # 1
NSF 600 Y
UL Pipe Size 14"
UL Valve Size Not rated
UL # of Coats 1 to 2
UL Max DFT 300 mils
UL Cure Time 4 hours
UL Thinner N/A

Polyclad 767

Tank Ratings
System # 1
NSF 600 Y
UL Tank Size 1000 gallons
UL # of Coats 1
UL Max DFT 120 mils
UL Cure Time Not Listed
UL Thinner N/A
Pipe, Valves, and Fittings
System # 1
NSF 600 Y
UL Pipe Size 12"
UL Valve Size 12"
UL # of Coats 1
UL Max DFT 120 mils
UL Cure Time Not Listed
UL Thinner N/A

Polyclad 767 Slow Set

Tank Ratings
System # 1
NSF 600 Y
UL Tank Size 1000 gallons
UL # of Coats 1
UL Max DFT 120 mils
UL Cure Time Not Listed
UL Thinner N/A
Pipe, Valves, and Fittings
System # 1
NSF 600 Y
UL Pipe Size 12"
UL Valve Size 12"
UL # of Coats 1
UL Max DFT 120 mils
UL Cure Time Not Listed
UL Thinner N/A

Polyclad 767 Fast Set

Tank Ratings
System # 1
NSF 600 Y
UL Tank Size 1000 gallons
UL # of Coats 1
UL Max DFT 120 mils
UL Cure Time Not Listed
UL Thinner N/A
Pipe, Valves, and Fittings
System # 1
NSF 600 Y
UL Pipe Size 12"
UL Valve Size 12"
UL # of Coats 1
UL Max DFT 120 mils
UL Cure Time Not Listed
UL Thinner N/A

*All Systems Certified by UL to Meet the Requirements of NSF 61/NSF 600